0. 设置topo python3 ocsdiag.py -i 10.57.216.95,10.57.216.96,10.57.216.97,10.57.216.98 -e 2,4,6,8 -c topo-config -p 32 1. ocs link reset ocs_link_reset -i 10.57.216.95,10.57.216.96,10.57.216.97,10.57.216.98 -e 2,4,6,8 1. 设置low freq 128 ,high freq 0 (最大) python3 ocsdiag.py -i 10.57.216.97 -e 8 -s all -c reg-wt -p lowfreq_eq -v 128 python3 ocsdiag.py -i 10.57.216.97 -e 8 -s all -c reg-wt -p highfreq_eq -v 0 2. 设置tia_peak 为 100,全局的lane 0和lane 3设置为0(最大) python3 ocsdiag.py -i 10.57.216.98 -e 8 -s all -c tia-peak-tune 3. 校准ibias (onoc) python3 ocsdiag.py -i 10.57.216.98 -e 8 -s all -c ibias-auto-tune 3.1 校准ibias (onet) python3 ocsdiag.py -i 10.57.216.98 -e 4 -s all -c ibias-auto-tune -p 10.57.216.96 python3 ocsdiag.py -i 10.57.216.96 -e 4 -s all -c ibias-auto-tune -p 10.57.216.98 4. 校准mgc onoc python3 ocsdiag.py -i 10.57.216.98 -e 8 -c rtmr-prbs python3 ocsdiag.py -i 10.57.216.98 -e 8 -s all -c mgc-auto-tune 4.1 校准mgc onet tx端: python3 ocsdiag.py -i 10.57.216.98,10.57.216.96 -e 4 -c rtmr-prbs rx端: python3 ocsdiag.py -i 10.57.216.96 -e 4 -s all -c mgc-auto-tune python3 ocsdiag.py -i 10.57.216.98 -e 4 -s all -c mgc-auto-tune 5. 查看retimer 误码情况 python3 ocsdiag.py -i 10.57.216.97 -e 8 -c vcmd -p "rtmr all" 6. 查看眼图情况 python3 ocsdiag.py -i 10.57.216.97 -e 8 -c vcmd -p "rtmr 1 eye 1 a" python3 ocsdiag.py -i 10.57.216.97 -e 8 -c vcmd -p "rtmr 2 eye 1 a" python3 ocsdiag.py -i 10.57.216.97 -e 8 -c vcmd -p "rtmr 3 eye 1 a" python3 ocsdiag.py -i 10.57.216.97 -e 8 -c vcmd -p "rtmr 4 eye 1 a" 如果眼偏下,则op_current需要调小。 7. 保存配置 先用vgc = 255,校准,然后手动改为200,发现recovery没增加了。